  • Model: IDM-6520
  • Serial port: 1-Ch RS-485 / 422
  • DP Port: PROFIBUS DP/V0
  • Power supply: DC9~36V, Max 50mA @ DC24V
  • Product description: IDM-6520 gateway is a converter from PROFIBUS DP protocol to Modbus RTU / ASCII protocol, and the data exchange between Modbus RTU / ASCII protocol and PROFIBUS DP protocol. Its PROFIBUS DP is a s
  • INQUIRY
Product introduction
IDM-6520 gateway is a converter from PROFIBUS DP protocol to Modbus RTU / ASCII protocol, and the data exchange between Modbus RTU / ASCII protocol and PROFIBUS DP protocol. Its PROFIBUS DP is a slave interface, which can be connected to PROFIBUS DP master station device such as Siemens PLC, and can solve the data communication problem between serial port device of Modbus RTU / ASCII protocol and PROFIBUS DP master station. Devices with RS-485 interface and supporting Modbus RTU / ASCII protocol can be connected to the field PROFIBUS DP bus using IDM-6520 gateway.
Technical specifications
MODBUS
Serial Port Mode: Modbus master and slave
Serial Port Type: 2-wire RS-485 and 4-wire RS-422
Baud Rate : 1200~115.2Kbps
Communication Parameters: 7,8 Data bits No, Odd, Even Parity bit 1 or 2 Stop bits
Protection : 1500V photoelectric isolation, 600W surge protection
Protocol: Modbus RTU, Modbus ASCII
Function Code: 01/02/03/04/05/06/15/16
Maximum Station: 31
PROFIBUS DP
Slave Protocol: PROFIBUS DP/V0
Baud Rate: 9.6Kbps~12Mbps Self-adaption
Protection : 1500V photoelectric isolation, 600W surge protection
Data Area :
Max Input Bytes ≤ 244 Bytes
Max Output Bytes ≤ 244 Bytes
Max Data Bytes ≤ 296 Bytes
Maximum Slot: 40
Working Voltage: DC9~36V,Max 50mA @ DC24V
Environment
Operating temperature: -40~85℃
Relative humidity: 5~95%  no condensed
Storage temperature: -45~125℃
Installation: 35mm DIN-Rail
Shape size: 124x78.5x32 (L * W * H, mm)
Interface definition
Power
V+: Power input positive
V-: Power input negative
PE: Grounding terminal
RS-485/422
T+:     RS-422 TX+
T-:      RS-422 TX-
GND:  Signal ground
R+/A: RS-422 RX+ / RS-485+
R-/B:  RS-422 RX- / RS-485-
PROFIBUS DP
DB9 - 3 RXD / TXD-P, Receive / send data - positive (line B)
DB9 - 8 RXD / TXD-N, Receive / send data – negative (line A)
DB9 - 5 DGND, Data Ground (reference VP)
DB9 - 6 VP, Supply voltage - Positive (5V)
LED
PWR: Power indication, On: the power supply is normal
DP:    DP network status indication, Normally on: communication is normal. Flashing or Off: communication error.
TX:    Serial port sending data indication, on: data sending
RX:    Serial port receiving data indication, on: receiving data
Setting of slave station address (DP address)
The PROFIBUS DP interface of IDM-6520 is a slave interface. When using, the user needs to set the slave address through X1 and X16 dial switches.
X1 :Low address switch.
X16:High address switch.
Slave address = (X16 * 16) + X1
If X1 switch is turned to 3 and x16 switch is turned to 0, it means that the address of the gateway in DP network is set to 0 * 16 + 3 = 3. If X1 switch is turned to 4 and x16 switch is turned to 1, it means that the address of the gateway in DP network is set to 1 * 16 + 4 = 20. The valid address range of PROFIBUS DP slave station is 1-125.